Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual
Page 54

BluCube
™
Condensing Unit
54
Condensing Units
Technical Manual : 7206188 V1.6.0_07 2014
Mechanical Data - Heat Pump Fixed Capacities Continued
CUR092V29-1HP-0
CUR122V35-1HP-0
CUR122V40-1HP-0
Capacity
Nominal Cooling Capacity
(1)
kW
28.7
39.7
44.1
Nominal Heating Capacity
(2)
kW
26.4
35.5
39.2
Capacity Steps
1
1
1
Dimensions
– W x D x H
(3)
mm
922 x 764 x 1736
1222 x 764 x 1736
1222 x 764 x 1736
Masses
– Machine / Operating
(4)
kg
262
316
324
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint
– Light Grey (RAL 7035)
Material/Colour
Heat Pump Evaporator / Condenser
Rifled Copper Tube/Louvered Hydrophilic Coated Aluminium Fins
Fan Motor
Axial
Motor Type
AC 1ph
AC 3ph
AC 3ph
Quantity x Motor Size
kW
1 x 0.6
1 x 1.97
1 x 1.97
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
895
1330
1330
Maximum Airflow
m³/s
2.0
3.5
3.5
Compressor
Compressor Type
Fixed Capacity Scroll
Quantity
1
1
1
Oil Charge Volume
l
3.3
3.3
3.6
Oil Type
Polyolester
Refrigeration
Single Circuit - 2 pipe configuration
Refrigerant control and type
Optional REEV package
Refrigerant type
R410A
Holding Charge
Inert Gas
Coil Volume
l
18.67
21.65
21.65
Refrigerant Charge
(5)
kg
6.82
7.15
7.15
Connections
Liquid (sweat)
in
1/2
1/2
5/8
Suction / Discharge (sweat)
in
7/8
7/8
1 1/8
Optional Extras
EC Fan
Quantity x Motor Size
kW
1 x 0.72
1 x 1.85
1 x 1.85
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
1000
1230
1230
Maximum Airflow
m³/s
2.3
3.5
3.5
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1750
1222 x 764 x 1750
1222 x 764 x 1750
Masses
– Machine / Operating
(3)
kg
254
308
316
Short Case Axial Fan
Designed to 75Pa ESP
Quantity x Motor Size
kW
1 x 1.4
N/A
N/A
Diameter
mm
560
N/A
N/A
Maximum Fan Speed
RPM
1330
N/A
N/A
Maximum Airflow
m³/s
2.8
N/A
N/A
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1753
N/A
N/A
Masses
– Machine / Operating
(3)
kg
268
N/A
N/A
REEV Selection
E²V - 35
E²V - 45
E²V
– 45
(1) Evaporating temperature 7°C, Ambient 35°C with an AC fan matched with a REEV package
All performance data is supplied in accordance with BS EN 14511-1:2013
(2) Condensing temperature 50°C, Ambient 5°C with an AC fan matched with a REEV package
(3) Overall dimensions for clearance
(4) Unit mass excludes a refrigerant charge
(5) For guidance only