Mechanical data cooling only modulating capacities, Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual
Page 39

Condensing Units
BluCube
™
Condensing Units
39
Technical Manual : 7206188 V1.6.0_07_2014
Mechanical Data Cooling Only Modulating Capacities
CUR092V16-VCO-0
CUR092V20-VCO-0
CUR092V25-VCO-0
Capacity
Nominal Cooling Capacity
(1)
kW
15.6
20.3
24.8
Capacity Steps
16-100%
16-100%
16-100%
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1736
922 x 764 x 1736
922 x 764 x 1736
Masses
– Machine / Operating
(3)
kg
219
220
241
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint
– Light Grey (RAL 7035)
Material/Colour
Condenser
Rifled Copper Tube/Louvered Hydrophilic Coated Aluminium Fins
Fan Motor
Axial
Motor Type
AC 1ph
AC 1ph
AC 1ph
Quantity x Motor Size
kW
1 x 0.6
1 x 0.6
1 x 0.6
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
895
895
895
Maximum Airflow
m³/s
2.0
2.0
2.0
Compressor
Compressor Type
Modulating Capacity Scroll
Quantity
1
1
1
Oil Charge Volume
l
1.9
1.9
3.2
Oil Type
Polyolester
Refrigeration
Single Circuit - 2 pipe configuration
Refrigerant control and type
Optional REEV package
Refrigerant type
R410A
Holding Charge
Inert Gas
Coil Volume
l
18.59
18.59
18.59
Refrigerant Charge
(4)
kg
6.81
6.81
6.81
Connections
Liquid (sweat)
in
3/8
1/2
1/2
Suction (sweat)
in
7/8
1 1/8
1 3/8
Optional Extras
EC Fan
Quantity x Motor Size
kW
1 x 0.72
1 x 0.72
1 x 0.72
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
1000
1000
1000
Maximum Airflow
m³/s
2.3
2.3
2.3
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1750
922 x 764 x 1750
922 x 764 x 1750
Masses
– Machine / Operating
(3)
kg
211
212
233
Short Case Axial Fan
Designed to 75Pa ESP
Quantity x Motor Size
kW
1 x 1.4
1 x 1.4
1 x 1.4
Diameter
mm
560
560
560
Maximum Fan Speed
RPM
1330
1330
1330
Maximum Airflow
m³/s
2.8
2.8
2.8
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1753
922 x 764 x 1753
922 x 764 x 1753
Masses
– Machine / Operating
(3)
kg
218
219
247
REEV Selection
E²V
– 24
E²V - 35
E²V - 35
(1) Evaporating temperature 7°C, Ambient 35°C with an AC fan matched with a REEV package
All performance data is supplied in accordance with BS EN 14511-1:2013
(2) Overall dimensions for clearance
(3) Unit mass excludes a refrigerant charge
(4) For guidance only