Heat pump heating fixed capacities, Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual
Page 51

Condensing Units
BluCube
™
Condensing Units
51
Technical Manual : 7206188 V1.6.0_07_2014
Heat Pump Heating Fixed Capacities
Winter Ambient (°C)
-5
0
5
10
15
Unit
Cond
Temp
(°C)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
CUR092V16-1HP-0
40
11.2
4.2
12.5
4.2
13.9
4.2
15.4
4.2
17.1
4.2
45
11.1
4.6
12.4
4.6
13.8
4.6
15.3
4.6
16.9
4.6
50
N/A
N/A
12.3
5.1
13.7
5.1
15.2
5.1
16.7
5.1
55
N/A
N/A
N/A
N/A
13.6
5.7
15.1
5.7
16.6
5.6
CUR092V20-1HP-0
40
16.0
6.0
17.8
6.0
19.7
6.0
21.7
6.0
23.9
6.0
45
15.8
6.5
17.7
6.6
19.6
6.6
21.5
6.6
23.7
6.6
50
N/A
N/A
17.4
7.1
19.4
7.2
21.3
7.2
23.4
7.2
55
N/A
N/A
N/A
N/A
N/A
N/A
21.1
7.8
23.1
7.8
CUR092V25-1HP-0
40
19.7
7.5
21.8
7.5
24.2
7.6
26.7
7.6
29.4
7.7
45
19.9
8.2
22.0
8.3
24.2
8.3
26.6
8.4
29.3
8.4
50
N/A
N/A
N/A
N/A
24.2
9.1
26.6
9.2
29.1
9.3
55
N/A
N/A
N/A
N/A
N/A
N/A
26.5
10.2
28.9
10.2
CUR092V29-1HP-0
40
21.6
8.2
24.0
8.3
26.5
8.3
29.2
8.4
32.0
8.5
45
21.7
9.0
24.0
9.1
26.4
9.2
29.0
9.3
31.8
9.3
50
N/A
N/A
N/A
N/A
26.4
10.2
28.9
10.2
31.6
10.3
55
N/A
N/A
N/A
N/A
N/A
N/A
28.8
11.3
31.4
11.4
CUR122V35-1HP-0
40
28.9
13.0
32.0
13.0
35.6
13.0
39.2
13.0
43.2
13.1
45
29.1
14.2
32.1
14.2
35.5
14.2
39.0
14.2
42.9
14.2
50
N/A
N/A
N/A
N/A
35.5
15.5
38.8
15.5
42.6
15.5
55
N/A
N/A
N/A
N/A
N/A
N/A
38.6
17.0
42.2
17.0
CUR122V40-1HP-0
40
32.0
14.0
35.4
14.2
39.4
14.3
43.3
14.4
47.8
14.6
45
32.2
15.2
35.5
15.3
39.3
15.5
43.1
15.6
47.5
15.7
50
N/A
N/A
N/A
N/A
39.2
16.8
42.9
16.9
47.1
17.0
55
N/A
N/A
N/A
N/A
N/A
N/A
42.7
18.4
46.7
18.5
Notes:
1
Output kW refers to the compressor duty.
All performance data is supplied in accordance with BS EN 14511-1:2013
2
Input kW refers to the compressor and fan input power only.