Dimensional & installation data, Dimensions / masses / positioning - horizontal, Condensers – Airedale Air Cooled Condensers R407C User Manual
Page 13: Standard condenser fan (mm) (c11 shown)

CONDENSERS
C11 - 45 / CS50 - 105
Condensers
13
Technical Manual: 6469597 V1.3.0 02_2013
Dimensional & Installation Data
DIMENSIONS / MASSES / POSITIONING - HORIZONTAL
Standard Condenser Fan (mm) (C11 Shown)
C
G
A
D
(3)
(4a)
F
B
(4b)
500
(2)
500
(2)
500
(2)
1800
(2)
(1)
(1)
(1)
(5)
E
Optional Short Case Axial Fan (mm) (SCAF) (C45 Shown)
DIMENSIONS (mm)
MASS (kg)
Standard Fan
Optional SCAF
Standard
Fan
Optional
SCAF
A
B
C
D
E
F
G
G1(6)
B
F
C11HI-H
648
550
1275
455
530
550
1118
N/A
675
640
51
61
C15HI-H
648
550
1275
455
530
550
1118
N/A
675
640
63
73
C20HI-H
848
645
1100
455
530
550
944
N/A
735
640
58
70
C25HI-H
848
645
1100
455
530
550
944
N/A
735
640
65
77
C35HI-H
1048
645
1650
455
530
550
1494
N/A
711
640
97
109
C45HI-H
1048
645
1650
455
530
550
1494
N/A
711
640
110
134
(1)
Airflow
(2)
Minimum clearances in mm
(3)
8mm fixing points
(4)
Service connections to left hand side of the unit: a = Liquid Outlet, b = Discharge Gas Inlet
(5)
Mains Electric Isolator, (CS50
– C105 located behind open side panel)
(6)
Additional support to sizes C80
– CS105
(7)
4 lifting eye bolts to unit top, sizes CS50
– CS105
(8)
Optional Short Case Axial Fan with integral duct fixing holes