FUNCTION LIST (LEVELS 1 to 4 and A)

Note: A Functions Menu is shown on page 3.

LEVEL 1

Function

Options

[Factory settings] shown in brackets

SELECT AUTOTUNE

(see pages 4/5)

tunE [oFF]

on PArK At.SP

Used to switch the Autotune feature on and off, to select

PArK

or Autotune at setpoint.

PArK

temporarily turns the output(s) off. To use select

PArK

and exit program mode. To

disable re-enter program at

tunE

and select

oFF

.

SP1 OPERATING PARAMETERS

bAnd

0.1 to * C/°F

[10ºC/18ºF/100 units]

SP1 proportional band/Gain or Hysteresis
* 100% (

Hi.Sc

) sensor maximum Proportional control eliminates the cycling of on-off

control. Output power is reduced, by time proportioning action, across the proportional
band.

int.t oFF

0.1 to 60 minutes

[5.0]

SP1 integral time/reset
Auto-corrects proportional control offset error

dEr.t oFF

1 - 200 seconds

[25]

SP1 derivate time/rate
Suppresses overshoot and speeds response to disturbances

dAC

0.5 - 5.0 x bAnd

[1.5]

SP1 derivative approach control dAC
Tunes warm-up characteristics, independent of normal operating conditions, by adjusting
when derivative action starts during start-up (smaller dAC value = nearer setpoint).

CyC.t A – – on.oF

0.1 - 81 sec

[20]

SP1 proportional cycle-time (see pages 9/10)
Determines the cycle rate of the output device for proportional control. Select

on.oF

for

ON/OFF mode.

oFSt

0 to * °C/°F/units

[0]

SP1 offset/manual reset
* ±50%

bAnd

. Applicable in proportional and ON/OFF mode with integral disable:

Int.t : oFF.

SP.LK [oFF]

on

Lock main setpoint
Locks the setpoint preventing unauthorised adjustment.

SP2 OPERATING PARAMETERS

(see page 6)

Function

Options

[Factory settings] shown in brackets

SEt.2

[

0] to * °C/°F/units

Adjust SP2 setpoint
* Deviation Alarms DV.hi, DV.Lo, bAnd 25% sensor maximum.
* Full scale alarms FS.hi, FS.Lo sensor range f/s

bnd.2

0.1 - * °C/°F/units

[2.0 °C/3.6°F 2 units]

Adjust SP2 hysteresis or proportional band/gain
(see

CyC.2

setting)

* 100% sensor f/s (

Hi.Sc

)

CyC.2 [on.oFF]

0.1–81 seconds

Select SP2 ON/OFF or proportional cycle-time
Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for proportional
mode.

LEVEL 2

MANUAL CONTROL MODES

Function

Options

[Factory settings] shown in brackets

SPI.P

0 to 100 % ‘read only’

Read SP1 output percentage power

hAnd [oFF]

1 to 100 % (not in ON/OFF)

SP1 manual percentage power control
For manual control should a sensor fail. Record typical SP1.P values beforehand.

PL.1

100 to 0 % duty cycle

[100]

Set SP1 power limit percentage
Limits maximum SP1 heating power during start-up and in proportional band.

PL.2

100 to 0 % duty cycle

[100]

Set SP2 percentage power limit (cooling)

SP2 OPERATING MODES

(see page 5)

SP2.A [nonE]

dV.hi dV.Lo bAnd FS.hi FS.Lo Cool EoP

Main SP2 operating mode

SP2.b [nonE]

LtCh hoLd nLin

Subsidiary SP2 mode: latch/sequence
Non-linear cool proportional band

LEVL 1

Will be affected by

dECP

settings in Level A

LEVL 2