Spectrex 20/20F - Fast UV/IR Flame Detector User Manual
Page 42
Spectrex Inc. - SharpEye
TM
UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005
36
Figure 11: UV/IR Detector Target Point
C
C
a
a
u
u
t
t
i
i
o
o
n
n
:
1 The following test will simulate a real fire condition and may activate the
extinguishing system or other alarms. If this is not desired, disconnect them
before the test and reconnect after the simulation.
Follow these instructions to simulate a fire:
1 Aim the Fire Simulator towards the detector’s “Target Point” (see Fig. 14)
2 For testing, keep a distance of at least 20 inches (50cm) from the detector.
3 Press the operation button once. Fire simulation will last for 20 seconds. The
detector will send an alarm signal.
4 For another fire simulation a 20 second time lapse is required between tests.
5 Make sure the optical window is clean and keep the Fire Simulator in the
storage case when not in use.