3 false alarms – Spectrex 20/20F - Fast UV/IR Flame Detector User Manual
Page 15
Spectrex Inc. - SharpEye
TM
UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005
9
3.3 False Alarms
The detector does not provide an alarm or a warning signal as a reaction to the
radiation sources specified at Table 3 below.
Notes:
IAD = Immune at any distance.
All sources are chopped from 0 to 20 Hz.
* Will be the same immunity distance as indicated when not chopped.
Table 3. Immunity to False Alarm Faults
Radiation Source
Immunity
Distance ft. (cm)
Sunlight IAD
Indirect or reflected sunlight
IAD
Vehicle headlights (low beam) conforming to MS53023-1
IAD
Vehicle Infrared light-MS 53024-1 or normal 50 watts
IAD
Incandescent frosted glass light, 100W
IAD
Flash light
IAD
Fluorescent light 40W (or two 20W)
IAD
Red dome light conforming to M251073-1 MS 51073-1
IAD
Radiation heater, 1500W
IAD
Radiation heater, 1000W with fan
IAD
Lit cigar or cigarette
IAD
Match, wood, stick including flare up
0.5ft (15cm)