beautypg.com

3 false alarms – Spectrex 20/20F - Fast UV/IR Flame Detector User Manual

Page 15

background image

Spectrex Inc. - SharpEye

TM

UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005

9

3.3 False Alarms


The detector does not provide an alarm or a warning signal as a reaction to the
radiation sources specified at Table 3 below.

Notes:
IAD = Immune at any distance.
All sources are chopped from 0 to 20 Hz.
* Will be the same immunity distance as indicated when not chopped.

Table 3. Immunity to False Alarm Faults

Radiation Source

Immunity
Distance ft. (cm)

Sunlight IAD
Indirect or reflected sunlight

IAD

Vehicle headlights (low beam) conforming to MS53023-1

IAD

Vehicle Infrared light-MS 53024-1 or normal 50 watts

IAD

Incandescent frosted glass light, 100W

IAD

Flash light

IAD

Fluorescent light 40W (or two 20W)

IAD

Red dome light conforming to M251073-1 MS 51073-1

IAD

Radiation heater, 1500W

IAD

Radiation heater, 1000W with fan

IAD

Lit cigar or cigarette

IAD

Match, wood, stick including flare up

0.5ft (15cm)