Spectrex Inc. - SharpEye™ UV Flame Detector Manual – TM 20/20UB Rev. E, August 2004

22

6.5 Detector Mounting

The detector may be mounted on a simple fabricated bracket, or preferably the
optional Swivel Mount, Model No. 20/20-003. The Swivel Mount enables the
detector to be rotated up to 40 degrees in all directions.

6.5.1 Swivel Mount Kit

Table 8: Mounting according to US Version

Item

QTY

Type /Model

Location

Swivel Mount

1

20/20-003

Screw

4

1/4” -20UNC Detector - Holding plate

1/4” Spring Washer

4

1/4”

Detector - Holding plate

Table 9: Mounting according to EU Version

Item

QTY Type /Model

Location

Swivel Mount

1

20/20-003-1

Screw

4

M6 x 1P

Detector - Holding plate

Spring Washer

4

M6

Detector - Holding plate

6.5.2 Swivel installation (Figure 4a and 4b)
1 Place the swivel mount (Item 6) in its designated location and secure it with

four (4) M6 or 1/4” screws, placed 3.0 in. (76.2 mm.) apart on swivel mount
plate (Item 10).

Note

: Skip this step if the Swivel Mount is already installed. Also detector

removal for maintenance purpose does not require Swivel Mount removal.

2 Unpack the detector carefully

3 Place the detector with its conduit inlets pointing down on the holding plate

of the Swivel Mount (Item 7). Secure the detector to the Swivel Mount by
four (4) 1/4”-20UNC screws or M6 x 1P (Item 9) with 1/4” (M6) spring
washers enclosed with the Swivel Mount Kit.
Use 3/16 Hex Key for 1/4” screws or No. 5 Hex Key for M6 screws.

4 Tighten the three locking 3/8"-24UNF screws (item 8) of the swivel mount

ring until the friction in the ball joint holds the detector in its position,
maintaining the ability to be moved by hand-applied force (Use 3/16" HEX
KEY).

5 Point the detector towards the protected area and make certain that the view

of the area is not obstructed. Secure the detector in that position by
tightening the locking screws of the swivel mount ring.

The detector is now correctly located and aligned, and ready for connecting to
the system.