4.3 Mode Selection

The detector has 2 DIPswitches, which enables the user to adapt the detector’s
operation to specific applications:

• Function switch (SW1)

• Alarm Delay Switch (SW2)


4.3.1 Function switch (SW1)
The user can select the desired mode of operation by means of this switch
according to Table 4.

Table 4. Function Switch SW1

SW ON Position

OFF Position

1

Alarm Signal Latching enabled. Reset
of the Alarm signal is performed by
momentary disconnection of power
supply or manual BIT activation.

Alarm Signal Latching disabled
(default).

2

Automatic & Manual BIT can be
performed (default).

Only Manual BIT can be
performed.

3

Not Used

4

Accessory Relay used by the Warning
level.

Accessory Relay used in parallel
to the Alarm Relay (default).

5

Not Used

6

Following a successful Manual BIT
sequence:
Alarm Relay is activated and the
4-20mA output turns to 20mA for
approximately 3 seconds (default).

Following a successful Manual
BIT sequence

(1),(2)

:

Alarm Relay is not activated

7

Following a successful Manual BIT
sequence

(2)

:

Accessory Relay is activated and the
4-20mA output turns to 16mA for
approximately 3 seconds

(3)

(default).

Following a successful Manual
BIT sequence

(2)

:

Accessory Relay is not activated.

8

Accessory Relay used as EOL relay.

Accessory Relay function in
accordance with the position of
SW1-4 (default).

Notes

:

1 The BIT sequence may last up to 7 seconds. Verify that all eight (8) switches

are in the appropriate setting (ON/OFF), to achieve the required functional
mode of operation.

2 SW1-2, SW1-6, SW1-7 are function only for model 20/20UB. Model 20/20U

does include BIT.

3 If both SW1-6 and SW1-7 are at on position the 4-20mA output is 20mA

(Alarm Level) after successful manual BIT.