Spectrex Inc. - SharpEye™ UV Flame Detector Manual – TM 20/20UB Rev. E, August 2004

14

4.5 Built-In-Test (refer to 2.5)

a. Principles
The detector’s Built In Test (BIT) checks the following:

• Electric circuitry

• Sensor

• Window cleanliness


The detector can be set to perform the BIT automatically and manually
(SW1-2 = ON) or manually only (SW1-2 = OFF).

b. Principles
If the BIT succeeds, the detector’s status turns to Normal.
If the BIT fails, a second BIT is executed after a delay of 6 seconds.
If the second BIT succeeds, the detector’s status turns to Normal; otherwise the
status is turned to Fault.

c. Manual BIT only (SW1-2= OFF):
The BIT is initiated manually by momentarily connecting terminal No. 3 with
terminal No. 2.
A successful manual BIT activates the following:

• Fault Relay is closed.

• Alarm Relay is activated for 3 seconds (only if SW1-6 = ON).

• Accessory Relay is activated for 3 sec (only if SW1-7 = ON).

• 4-20mA Output current will be 20mA (only if SW1-6 = ON) or 16mA

(Only if SW1-7 = ON and SW1-6 = OFF).

• The yellow LED blinks at 0.5Hz rate.


Unsuccessful BIT activates the following:

• Fault Relay is released.

• 4-20mA output indicates Fault condition (2mA).

• The yellow LED blink (at 2Hz rate)

Important Note!

If SW1 switches 7 or 6 are in their “ON” position the Alarm and
Accessory Relays will be activated during a MANUAL BIT, therefore,
automatic extinguishing systems or any external devices that may be
activated during BIT must be disconnected.