Appendix E - Long Range IR3 Fire Simulator

Figure 21: Fire Simulator

Product Description
The SharpEye IR3 Long Range Fire simulator 20/20-310 is designed specifically
for use with the IR3 flame detectors. The Fire Simulator emits IR radiation in a
unique sequential pattern corresponding and recognizable by the IR3 detector as
fire. This allows the IR3 detectors to be tested under real fire conditions without
the associated risks of an open flame. There is a specially designed beam
collimator model number 20/20-190 used for extended range.

Unpacking
In addition to the delivery form, there should be the following contents:

• Fire Simulator with built in batteries

• Battery charger

• Optional Beam Collimator

• Storage Case


Operating Instructions
WARNING:
Do not open the Fire Simulator to charge the batteries or for any other reason in a
hazardous area.

CAUTION:
The following test will simulate a real fire condition and may activate the
extinguishing system or other alarms. If this is not desired, disconnect them
before the test and reconnect after the simulation.