Spectrex 20/20SI Triple IR (IR3) Flame Detector User Manual
Page 21
Spectrex Inc. - SharpEye
TM
IR3 Flame Detector Manual – TM 20/20I, Rev. (6) August 2004
13
4.3.2 Address switch (SW2) (Optional):
The address switch provides 64 alternative addresses that can be used with the
RS-485 communication link. See tables 8 and 9.
Table 8: Address Switches SW2
SWITCH
Description
1
Address bit 0 (LSB)
2 Address
bit
1
3 Address
bit
2
4 Address
bit
3
5 Address
bit
4
6
Address bit 5 (MSB)
Legend:
0 = OFF
1 = ON
LSB = Least Significant Bit
MSB = Most Significant Bit.
SWITCH SW2-7 and SWITCH SW2-8 are unused.
Table 9: SW2 Address Setting
Address
SW2-6
SW2-5
SW2-4
SW2-3
SW2-2
SW2-1
0
OFF OFF OFF OFF OFF OFF
1
OFF OFF OFF OFF OFF ON
2
OFF OFF OFF OFF ON OFF
3
OFF OFF OFF OFF ON ON
4
OFF OFF OFF ON OFF OFF
5
OFF OFF OFF ON OFF ON
.
.
.
.
.
.
62 ON ON ON ON ON OFF
63 ON ON ON ON ON ON
Note
: Default address = 0