Spectrex 20/20SI Triple IR (IR3) Flame Detector User Manual
Page 20
Spectrex Inc. - SharpEye
TM
IR3 Flame Detector Manual – TM 20/20I, Rev. (6) August 2004
12
4.3.1 Function switch (SW1):
The user can select the desired mode of operation by means of this switch
according to table 6:
Table 6: Function Switch SW1
SW.
ON Position
OFF Position
1
Alarm latching - enabled
Alarm latching – disabled (default)
2
Accessory relay activated at warning
level
Accessory relay activated at
detection level (together with Alarm
relay) - (default)
3
Automatic & manual BIT (default)
Manual BIT only
4
Successful manual BIT activates the
Alarm relay and the 4-20mA output
turns to 15mA for approximately 3
seconds (default)
Successful manual BIT does not
activate the Alarm relay.
5
Successful manual BIT activates the
accessory relay and the 4-20mA
output turns to 10mA for
approximately 3 seconds (default)
Successful manual BIT does not
activate the Accessory relay.
6*
Sensitivity range – see table 7 below
(default)
Sensitivity range - see table 7
7*
Sensitivity range - see table 7 below Sensitivity range - see table 7
(default)
8
Accessory relay used as End Of
Line.
Accessory relay operates in
accordance with the settings of
SW1(default)
* See Table 7 for sensitivity range setting.
Table 7: Sensitivity range
Sensitivity
Range
SW1-7
SW1-6
1 (lowest)
50 ft (15m)
OFF
OFF
2 100
ft
(30m)
OFF
ON
3 150ft
(45m)
ON
OFF
4 (highest)
200ft (60m)
ON
ON