Appendix A - Wire Selection Tables


General Instructions For Electrical Wiring

1. Refer to Table 14 to determine the required wire gauge for general wiring,

such as relay wiring. Calculate the permitted voltage fall with respect to
loads current, wire gauge and length of wires.

2. Refer to Table 15 to select wire gauge for power supply wires. DO NOT

connect any circuit or load to detectors’ supply inputs.

Table 14: Maximum DC resistance at 68˚F for copper wire

AWG # mm

2

Ohm per 100 ft.

Ohm/100

meter

26 0.12

-

0.15 4.32

14.15

24 0.16

-

0.24 3.42

11.22

22

0.30 - 0.38

1.71

5.60

20

0.51 - 0.61

1.07

3.50

18

0.81 - 0.96

0.67

2.20

16

1.22 - 1.43

0.43

1.40

14

1.94 - 2.28

0.27

0.88

12

3.09 - 3.40

0.17

0.55

10

4.56 - 6.64

0.11

0.35

A. Select "Number of detectors" connected in one circuit.
B. Select "wiring length" per your installation requirements.
C. Refer to "power supply range" for voltage extreme applied.

Table 15. Wiring length in feet (meter)

No. of
Detectors

Recommended Wire Diameter

Power Supply
Range (VDC)

24

18

16

14

-

-

22-32

20

18

16

14

-

-

22-32

16

20

18

16

14

-

22-32

12

20

18

16

14

-

20-32

8 20

18

16

14

-

20-32

4

and

less

20

18 16 16 14

20-32

Feet

164

328 492 656 820

(meter)

(50)

(100) (150) (200) (250)

Max. Length from Power Supply to Last

Detector