Spectrex 20/20MI - Mini Triple IR (IR3) Flame Detector User Manual
Page 58
Spectrex Inc. - SharpEye
TM
Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011
50
Flame Response Sensitivity Test
All four samples of the Model 20/20MI-3 were exposed to the standard test
consisting of a 12 in. x 12 in. (0.3m x 0.3m) pan fire with fuels noted below. The
tests were conducted at FM Approvals in Norwood, MA, and the average results
for all four samples are as follows:
Distance to
Fire
Detector
Model
Fuel
Ft.
m
Sensitivity
setting
Response
(seconds -
average
20/20 MI-3
n-heptance
33
10
10
3.0
20/20 MI-3
n-heptance
24.7
7.5
7.5
4.2
20/20 MI-3
n-heptance
16.5
5
5
4.1
20/20 MI-3
n-heptance
8.2
2.5
2.5
8.2
20/20 MI-3
Diesel
23.1
7
10
3.8
20/20 MI-3
Diesel
17.3
5.3
7.5
5.5
20/20 MI-3
Diesel
11.5
3.5
5
6.4
20/20 MI-3
Diesel
5.7
1.7
2.5
9.2
20/20 MI-3
Ethyl Alcohol
24.8
7.5
10
4.6
20/20 MI-3
Ethyl Alcohol
18.5
5.6
7.5
3.2
20/20 MI-3
Ethyl Alcohol
12.4
3.8
5
4.8
20/20 MI-3
Ethyl Alcohol
6.1
1.8
2.5
3.6
20/20 MI-3
Jet A
23.1
7
10
1.9
20/20 MI-3
Jet A
17.3
5.3
7.5
4.3
20/20 MI-3
Jet A
11.5
3.5
5
6.1
20/20 MI-3
8 in.(20cm) dia. Pan
polypropylene pellets.
8 2.4
10
1.9
Field of View Test
One sample of the Model 20/20 MI-1, which has an identical enclosure to the
20/20 MI-3 and is considered representative of the series, was exposed to the 12
in. x 12 in. (0.3 m. x 0.3 m.) N-heptane pan fire during which time the viewing
angle was varied +/-50º from the centerline along the horizontal and vertical axes.
The following results were obtained:
Angle (Approximate)
Distance
Average Response Time
On centerline
33 ft. (10m.)
3 sec.
+ 50º horizontal
16.5 ft. ( 3 m.)
8.7 sec.
- 50º horizontal
16.5 ft. ( 3 m.)
8.1 sec.
+ 50º vertical
16.5 ft. ( 3 m.)
8.8 sec.
- 50º vertical
16.5 ft. ( 3 m.)
12 sec.