Spectrex 20/20MI - Mini Triple IR (IR3) Flame Detector User Manual
Page 20
Spectrex Inc. - SharpEye
TM
Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011
12
3.3 False Alarms Prevention
The detector will not provide an alarm or a warning signal as a reaction to the
radiation sources specified below.
Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20Hz.
Table 5: Immunity To False Alarm Sources
Radiation Source
Immunity
Distance ft(m)
Sunlight IAD
Indirect or reflected sunlight
IAD
Incandescent frosted glass light, 100 W
IAD
Incandescent clear glass light, rough service, 100 W
IAD
Fluorescent light with white enamel reflector, standard office or
shop, 40 W (or two 20 W)
IAD
Electric arc [12mm (15/32 in) gap at 4000 V alternating current,
60 Hz]
IAD
Arc welding [4 mm (5/32 in) rod; 240 A]
See Table 6, 7
Ambient light extremes (darkness to bright light with snow, water,
rain, desert glare and fog)
IAD
Bright colored clothing, including red and safety orange.
IAD
Electronic flash (180 watt-seconds minimum output)
IAD
Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55 or
equivalent)
6.5 (2)
Flashlight (MX 991/U)
IAD
Radiation heater, 1500 W
IAD
Radiation heater, 1000 W with fan
IAD
Quartz lamp (1000 W)
10 (3)
Mercury vapor lamp
IAD
Grinding metal
IAD
Lit cigar
1 (0.3)
Lit cigarette
1 (0.3)
Match, wood, stick including flare up
10 (3)