22

5.3 Environmental Specifications

High Temperature

Design to meet MIL-STD-810C, method 501.1 procedure II
Operating temperature:

+160 °F (+70 °C)

Storage temperature:

+185 °F (+85 °C)

Low Temperature

Design to meet MIL-STD-810C, method 502.1, procedure I
Operating temperature:

-40 °F (-40 °C)

Storage temperature:

-65 °F (-55 °C)

Humidity

Design to meet MIL-STD-810C, method 507.1, procedure IV

Relative humidity of up to 95% for the operational temperature range.

Salt Fog

Design to meet MIL-STD-810C, method 509.1, procedure I

Exposure to a 5% Salt Solution Fog for 48 hours.

Dust

Design to meet MIL-STD-810C, method 510.1, procedure I
Exposure to a dust concentration of 0.3 frames/cubic ft. at a velocity of
1750 fpm, for 12 hours.

Vibration

Design to meet MIL-STD-810C, method 514.2, procedure VIII
Vibration at an acceleration of 1.1g within the frequency range of 5-30 Hz,
and an acceleration of 3g within the frequency range of 30-500 Hz.

Mechanical Shock

Design to meet MIL-STD-810C, method 516.2, procedure I

Mechanical Shock of 30g half-sin wave, for 11 msec.

Electromagnetic Compatibility (EMC):

This product is in conformance with EMC directive 89/336/EC.

Radiated Emission

EN61000-6-3

Conducted Emission

EN61000-6-3

Radiated Immunity

EN61000-4-3

Conducted Immunity

EN61000-4-6

ESD

EN61000-4-2

Burst

EN61000-4-4

Surge

EN61000-4-5