beautypg.com

D.1.5, Technical specifications, Tilt mount - p/n 40/40-001 – Spectrex 40/40M Multi IR Flame Detector User Manual

Page 72: Figure 18: tilt mount, D.1.5 technical specifications

background image

Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

60

Tilt Mount - P/N 40/40-001

D.1.5 Technical Specifications

Mechanical

Explosion Proof Enclosure:

AFM(designed to meet)

Class I, Division 1 & 2 Groups B, C and D

Class II, Division 1 & 2 Groups E, F and G

ATEX EX II2G NEMKO 02ATEX255

EExd IIB T5 50°C per En 50-014 & EN50-018

Electrical

Power: 8 VDC Max.

6 x Rechargeable 1.2 VDC NiCd Batteries

Current: 2.5A Avg.

Charge: 400 mA for 14 Hours

Environment

Temperature Range:-4 to +122ºF (-20 to +50ºC)

Vibration Protection: 1g (10-50hz)

Water and Dust: IP 67 per EN 60529

Physical

Dimensions: 11.5 x 10.1 x 3.9 in

(292 x 258 x 100 mm)

Weight; 7.5 lb. (3.4 Kg)

D.2

Tilt Mount - P/N 40/40-001

The Tilt mount provides accurate directional selection for optimum area
coverage.

Figure 18: Tilt Mount