Internal Detector Tests

17

1.6.2.2 Automatic BIT

The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.

All outputs of BIT results will function as described in Table 10 and Table 11,
and the BIT will be automatically executed every 1 minute.

This continues until a successful BIT occurs, when the detector resumes
normal operation.

Table 10: Results of a Successful BIT

Output

Result

Fault relay

Wiring options 1, 2, 4: remains CLOSED

Wiring options 3 and 5: remains OPEN

0-20mA
output

Wiring option 1, 2, 3: Normal (4 mA)

Power LED

Green, Flashing, 1 Hz On (Normal)

Table 11: Results of an Unsuccessful BIT

Output

Result

Fault relay

Wiring option 1, 2, 4: changes to Open

Wiring option 3 and 5: changes to Closed

0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED

Yellow, Flashing, 4 Hz

BIT procedure

Performed every 1 minute