Performance Considerations

7

For more details and guidelines for configuring, installing, operating and

service – see SIL-2 Features on page 65 and TÜV Report No.
968/EZ348.00/009.

1.4.5.4 EN54-10

The 40/40M Flame Detector is certified to EN54-10 and CPD.

The detector has been tested and approved per EN54-10 by VdS.

This test includes functional test, environmental test, EMI/EMC test and

software check.

For more details see VdS Reports No’s. BMA 12117 and BMA 12118.

1.5

Performance Considerations

This section describes performance aspects of the 40/40M and includes:

Detection Sensitivity, page 7

Cone of Vision, page 9

False Alarms Prevention, page 11

Visual Indicators, page 12

Output Signals, page 13

Detector Status, page 14

Auxiliary Relay as End-of-Line Resistor, page 15

1.5.1 Detection Sensitivity

Detection sensitivity is the maximum distance at which the detector reliably
detects a specific size of fire and typical type of fuel (standard fire).

1.5.1.1 Standard Fire

Defined as a 1ft

2

/ 0.1m

2

n-heptane pan fire, with maximum wind speed of

6.5 ft./sec (2 m/sec).

1.5.1.2 Sensitivity Ranges

The detector has four user-selectable sensitivity ranges. For each range
there are two response levels.

WARNING (Pre-alarm)

ALARM

The detection distance, for the WARNING level, is approximately 10% higher
than the ALARM distance.