beautypg.com

Spectrex 40/40M Multi IR Flame Detector User Manual

Page 48

background image

Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

36

Testing Procedures

2

Aim the Spectrex Fire Simulator Model 20/20-313 at the target point of
the detector (Figure 14), in a way that the radiation emitted by it is
facing directly towards the detector. (See Long Range Multi IR Fire
Simulator
on page 57).

3

Press the operation button once. After few seconds, a successful test
shows the results shown in Table 19.

Table 19: Results of Successful Fire Simulator Test

Component

Action

Notes

0-20mA

Turn to 20mA

For a few seconds and then return to
4mA

Alarm Relay

Activated

for a few seconds and then returns to
Normal

Auxiliary Relay

Activated

for a few seconds and then returns to
Normal

Fault Relay

Remains active
during the test

LED

Red, steady

The detector is now ready for operation.