3 . Time ON and Time OFF: Program the channel for an
ON event and an OFF event for the times you choose .
Do not connect a photo sensor . (For two channel units
photo sensor may be connected but also set select
switch to TIMER setting .)
Timed Override
Wiring a Tork SS410 to the remote override
connections provides an easy way to meet various
energy code requirements for indoor lighting . Include
the Tork #TRP to power the low voltage switch .
A Tork A502H may also be used to provide a low
cost 2 hour override .
INPUT CONNECTIONS
There are two removable terminal blocks on the rear of
the units . The terminal blocks, as viewed from the rear,
are labeled TB3 (left side, green), and TB2 (right side,
black) .
TB3 is used to connect the EPC-A to the unit . Wire
the terminal block from left to right, with the blue, black,
and red wires going to the EPC-A, wire length not to
when the light level is twice the preset footcandles .
(For two channel units also set select switch to PHOTO
setting .)
2 . Sunset ON and Time OFF: Program an ON event
at the earliest time you want to allow photo sensor to
begin to operate . Then program a night time OFF
event . (For two channel units also set select switch to
PHOTO setting .)
Example: ON at 3:00pm and OFF at 11:00pm MO –
SU . The photo sensor will take control at 3:00pm and
turn ON the load only when light level drops to the
preset footcandles, but timer will shut OFF the load at