Installation:
NOSHOK pressure transmitters/transducers may
be mounted in any plane with negligible effect on
performance. Although these units are designed
and manufactured to withstand substantial shock
and vibration, it is recommended that they be
mounted in an area of minimal vibration. Always
use a wrench on the wrench flats when installing.
NEVER use a pipe wrench on the housing or in the
area of the electrical connection.
Maintenance/Calibration:
NOSHOK pressure transmitters/transducers
require no maintenance. Recalibration is
dependent on the users Quality Assurance
Program. If no program is in place, NOSHOK
recommends a 1 year cycle.
Alignment Procedure (applies only to 100,
200, 615/616, and 640 series):
Using a pressure source and meter with adequate
accuracy, perform the following steps:
• Open sensor
• With no pressure applied,
adjust the “Z”
potentiometer for the
correct Zero output
• Apply the correct full scale
pressure to the unit
• Adjust the “S”
potentiometer for the
correct Span output
NWD 08-3
Span
Zero
SERIES 660
SERIES 800
4 mA to 20 mA, 2 wire
Power
Supply
+ Supply
Output
+ Output
Load Limitations
4 mA to 20 mA Output Only
Vmin = 10V + (.020 x R
L
)
R
L
= R
S
+ R
W
R
L
= Loop Resistance (ohms)
R
S
= Sense Resistance (ohms)
R
W
= Wire Resistance (ohms)
Series 800
4 mA to 20 mA
CONNECTION TYPE (CODE)
+ SUPPLY
+ OUTPUT
Hirschmann (8 or 14)
1
2
Hirschmann w/ Cable (1)
Red
Black
M12 x 1, 4-Pin (25)
1
3
Series 800
0-10 Vdc
CONNECTION TYPE (CODE)
+ SUPPLY
COMMON
+ OUTPUT
Hirschmann (8 or 14)
1
2
3
Hirschmann w/ Cable (1)
Red
Black
White
M12 x 1, 4-Pin (25)
1
3
4
Example: Red / 1 = Applicable color wire / din plug number.
Load Limitations
4 mA to 20 mA Output Only
Vmin = 10V + (.020 x R
L
)
R
L
= R
S
+ R
W
R
L
= Loop Resistance (ohms)
R
S
= Sense Resistance (ohms)
R
W
= Wire Resistance (ohms)
Series 660
4 mA to 20 mA
CONNECTION TYPE (CODE)
+ SUPPLY
+ OUTPUT
Mini-Hirschmann (7)
1
2
Mini-Hirschmann w/ Cable (1)
Red
Black
M12 x 1, 4-Pin (25)
1
3
Integral Cable (36)
Brown
Green
Wiring - M12 x 1 4-pin
round connector
Wiring - Mini-Hirschmann
connector
Series 660
1-5 Vdc, 0.1-10 Vdc
CONNECTION TYPE (CODE)
+ SUPPLY
COMMON
+ OUTPUT
Mini-Hirschmann (7)
1
2
3
Mini-Hirschmann w/ Cable (1)
Red
Black
White
M12 x 1, 4-Pin (25)
1
3
4
Integral Cable (36)
Brown
Green
White
Current output, 2 wire
Power
Supply
+ Supply
Output
+ Output
1
3
2
Power
Supply
+ Supply
Output
+ Output
Common
1
3
2
Voltage output, 3 wire
Current output, 2 wire
Power
Supply
+ Supply
Output
+ Output
Voltage output, 3 wire
Power
Supply
+ Supply
Output
+ Output
Common
0 Vdc to 10 Vdc, 3 wire
Power
Supply
+ Supply
Output
+ Output
Common