KYORITSU 3007A User Manual
Page 6
![background image](/manuals/369572/6/background.png)
3. SPECIFICATIONS
●
Measuring Range and Accuracy (at 23
±
5°C, relative humidity 45 -75%)
○
Insulation Resistance Ranges:
Nominal Output Voltage
250V
500V
1000V
Measuring
0 ~19.99M
Ω
0 ~19.99M
Ω
0 ~19.99M
Ω
Ranges
0 ~ 199.9M
Ω
0 ~ 199.9M
Ω
0 ~ 199.9M
Ω
0 ~ 1999M
Ω
0 ~ 1999M
Ω
0 ~ 1999M
Ω
Open-Circuit
250V DC
500V DC
1000V DC
Voltage
+20%,-0%
+20%,-0%
+20%,-0%
Nominal Current
1mA DC min.
1mA DC min.
1mA DC min.
at 0.25M
Ω
at 0.5M
Ω
at 1M
Ω
Short-Circuit
Current
1.5mA approx
20M
Ω
±
1.5%rdg
±
5dgt
200M
Ω
Accuracy
2000 0~1G
Ω
±
3%rdg
±
3dgt
M
Ω
1G~2G
Ω
±
10%rdg
±
3dgt
○
Continuity Ranges:
Ranges
20
Ω
200
Ω
2000
Ω
Measuring Ranges
0 ~ 19.99
Ω
0 ~ 199.9
Ω
0 ~ 1999
Ω
Open-Circuit
Voltage
7 ~ 12V approx
Measuring Current
at 0.2
Ω
~ 2
Ω
200mA min
Accuracy
±
1.5%rdg
±
5dgt
±
1.5%rdg
±
3dgt
○
AC Voltage Indication
0 ~ 600V
±
5%rdg
±
3dgt
―
5
―
2. FEATURES
MODEL-3005A/3007A are microprocessor controlled insulation-continuity
testers.
●
Designed to safety standards:
IEC 61010-1 Overvoltage CAT III 300V Pollution Degree 2
IEC 61010-2-31 (Safety requirements for hand-held probe assemblies)
●
Display with back light function to facilitate work at night or dimly lit
locations (Model 3007A only)
●
Bar graph to indicate measured results
●
Strap belt to make both hands' operation easier
●
Live circuit warning indication and buzzer
●
Auto discharge function
When insulation resistance is measured, electric charges stored in
capacitive circuits are automatically discharged after testing. Discharge
can be checked with live circuit warning.
●
Auto power off function
To prevent the instrument from being left powered on and conserve
battery power, the instrument automatically turns off approx. 10 minutes
after the last switch operation.
●
LOK mode (Model 3007A only)
The test current is removed once a stable reading is reached to prevent
unnecessary battery consumption.
―