beautypg.com

2 electrical connection: pactware, Electrical connections – KROHNE OPTIWAVE 7300C PROFIBUS PA User Manual

Page 6

background image

3

ELECTRICAL CONNECTIONS

6

OPTIWAVE 7300 C

www.krohne.com

02/2010 - 4000621701 - AD PROFIBUS PA OPTIWAVE 7300

3.2 Electrical connection: PACTware™

PACTware™ is an Open Source, open configuration software for all field devices. Use
PACTware™ to configure your device. For more data, refer to "Start-up" in the handbook.

Attach a HART

®

converter to the terminals shown in the illustration that follows. We recommend

the VIATOR converter that is available as an accessory for this device. Refer to the Handbook for
more data on accessories.

CAUTION!
Before you use PACTware

to configure the device, disconnect the device from the PROFIBUS

PA segment.

CAUTION!
The HART address of the device must be set to "1". If the device is not set to "1", the device will
not operate in PROFIBUS PA networks. Refer to the Handbook for more data on how to change
the HART address.

Figure 3-2: Electrical connection: PACTware™

1 PACTware™ terminals