Profibus pa data – KROHNE OPTIWAVE 7300C PROFIBUS PA User Manual
Page 4
2
PROFIBUS PA DATA
4
OPTIWAVE 7300 C
www.krohne.com
02/2010 - 4000621701 - AD PROFIBUS PA OPTIWAVE 7300
INFORMATION!
•
The data that follows is applicable only for fieldbus communication networks. For general
data, refer to the handbook.
•
Additional information (certificates, special tools, software, files...) and complete product
documentation is on the CD delivered with the device or can be downloaded free of charge
from the website (Downloadcenter).
Type
FMCW radar level transmitter
Output signal
Digital signal that agrees with the PROFIBUS PA communication protocol
Profile Ident
9700
Data blocks
Function blocks
7 (level, distance, level conversion, level mass, reflection, ullage conversion and
distance mass)
Communication Standard
PROFIBUS PA protocol that agrees with IEC 61158-2
Physical layer
Protocol
PROFIBUS PA protocol that agrees with IEC 61158-2, galvanically isolated
Physical layer types
Standard power signaling, bus powered, non I.S.
Other features
Bus interface with integrated reverse polarity protection
Electrical connections
Device power supply (24 V input)
18...30 VDC
Current consumption on
PROFIBUS network
20 mA
Input and output
Output data
Level, distance, level conversion, level mass, reflection, ullage conversion or
distance mass
Input data
None
Error current FDE
Typically 0 mA (FDE =Fault Disconnection Electronic)
Address range
0...125. Default address: 126. For more data, refer to
PROFIBUS PA address
on
page 9.