Start-up – KROHNE OPTIWAVE 5200 IECEx User Manual

Page 31

background image

START-UP

4

31

OPTIWAVE 5200 C/F

www.krohne.com

04/2013 - 4001906102 - AD IECEX OPTIWAVE 5200 R02 en

• Are the wetted components (gasket, flange and antenna) resistant to corrosion by the tank

product?

• Does the information given on the nameplate agree with the application?
• Did you connect the equipotential bonding system correctly?
• Ex d applications:

Ex d applications:

Ex d applications:

Ex d applications: Are the cable entries, plugs and adaptors Ex d-approved?

• Ex t applications:

Ex t applications:

Ex t applications:

Ex t applications: Are the cable entries, plugs and adaptors Ex t-approved?

• Ex ia applications:

Ex ia applications:

Ex ia applications:

Ex ia applications: Are you using an intrinsically-safe barrier within the correct parameters?

For more data, refer to

Ex ia equipment

on page 23. The electrical circuit characteristics must

not be more than the maximum intrinsically-safe values.

• Ex ic applications:

Ex ic applications:

Ex ic applications:

Ex ic applications: Are you using an intrinsically-safe barrier within the correct parameters?

For more data, refer to

Ex ic equipment

on page 28. The electrical circuit characteristics must

not be more than the maximum intrinsically-safe values.

• Did you install the correct cable entries? Is the terminal compartment correctly sealed?
• Does the optional purging system agree with Ex requirements?

WARNING!
Make sure that it is safe to supply electrical power. Do a start-up check: