Electrical connections, 2 how to connect the electrical cables, 3 supply voltage – KROHNE OPTIWAVE 5200 IECEx User Manual
Page 26
3
ELECTRICAL CONNECTIONS
26
OPTIWAVE 5200 C/F
www.krohne.com
04/2013 - 4001906102 - AD IECEX OPTIWAVE 5200 R02 en
3.6.2 How to connect the electrical cables
Cable entries are supplied on customer demand. If you supply the cable entries, this part must
have a degree of ingress protection IP≥6x (IEC 60529).
• Do not remove more than 6 mm / 0.2¨ of insulation from the wire.
• Connect the load resistor to the positive terminal of the power supply
• Ground the negative connection.
• If the load resistor has to be connected to the negative terminal, the loop resistance must not
be more than 350 ohms.
3.6.3 Supply voltage
Level transmitter with the 4...20 mA output option
Level transmitter with the PROFIBUS PA or FOUNDATION fieldbus output options
For more data, refer to
Maximum intrinsically-safe values for the electrical circuit
on page 23.
WARNING!
Use only Ex d-approved cable entries and plugs for Ex d applications. Use only Ex t-approved
cable entries and plugs for Ex t applications.
Do not remove more than 6 mm / 0.2
¨
of insulation from the wire.
CAUTION!
4...20 mA passive - HART output option:
4...20 mA passive - HART output option:
4...20 mA passive - HART output option:
4...20 mA passive - HART output option: Do not ground the positive connection.
INFORMATION!
For maximum intrinisically-safe values, refer to Maximum intrinsically-safe values for the
electrical circuit on page 23
.
Minimum voltage at
output terminal [VDC]
Maximum voltage at
output terminal [VDC]
Current output terminal
16
1
36
1
1 For a current output of 22 mA
Minimum voltage at
output terminal [VDC]
Maximum voltage at
output terminal [VDC]
Output terminal
Entity
9
24
FISCO
9
17.5