2. Electrical

installation

2.1

Location and connecting cables


Location

Do not expose the compact flow meter to direct sunlight. Install a sunshade if necessary.

Connecting cables

To conform to protection category requirements, observe the following recommendations:

Fit blanking plug PG 16 and apply sealant to unused cable entries.

In case if the terminal area is Eed, please use approved blanking plug.

Do not kink cables directly at cable entries.

Provide water drip point (U bend in cable).

Do not connect rigid conduit to cable entries.

If cables are a tight fit, enlarge inside diameter of cable gland by removing the appropriate
ring(s) from the seal.


2.2

Electrical Connection on converter without intrinsically safe outputs

Note information given on the instrument dataplate (voltage, frequency)!


Electrical connection in conformity with IEC 364 or equivalent national standard.


Special regulations apply to installation in hazardous areas. Please refer to separate "Ex"
installation instructions.


– The PE protective ground conductor must be connected to the separate U-clamp

terminal in the terminal box of the signal converter.


Do not cross or loop the cables in the terminal box of the signal converter. Use separate
(PG or NPT) cable glands for power and output cables.


– Ensure

that

the

screw thread of the round cover on the terminal box is well greased at

all times.

NOTE: The grease used must be non-corrosive to aluminium; typically it must be resin- and

acid-free.


– Protect sealing ring from damage.


5 6 4 4.1 4.2 11 12



N L AC
Outputs - + DC
connection PE
see Sect. 2.2
Power and signal connections for MFC 085 K

Please ensure that the information about power given on the
dataplate corresponds to the locally available mains voltage.