13 H54 Installation and operating instructions

9

Electrical signal output ESK II



9.1 Electrical

connection

The connecting terminals of the M9 display have a pluggable design and can be removed in order to

connect the lines.











9.2 HART

TM

communication with the ESK II

HART

TM

communication is not compellingly required in order to operate the ESK II.

When

HART

TM

communication is carried out with the ESK II, this does not by any means impair analog

measured value transfer (4...20mA).

Exception at Multidrop operation. In Multidrop operation a maximum of 15 instruments with HART

TM

function can be operated in parallel, whereby their current outputs are switched inactive (approx. 4 mA).















If a HART

TM

communicator (type Fisher Rosemount, Model 275) or a PC with HART

TM

modem is

used, the resistor which is connected in series (R

ext.

) has to exceed 250 Ohms.

In this type of operation the auxiliary power must amount to at least 18 V. The communicator or the PC

is connected as shown in the drawing above.

It can be operated optionally via the connecting terminals of the ESK II (2) or via an external resistance

(1) connected in series. The counter cannot be read out or operated by means of HART

TM

communication!



9.3

Technical data of ESK II

Auxiliary power

12 (18 * ) to 30 V DC

Measurement signal

4.00 to 20.00 mA for 0 to 100 % flow value

>

20.8

mA

for

alarm

status

Auxiliary power influence <

0.1%

Dependency on external resistance

< 0.1%

Temperature

influence

<

5

µA / K

Max. external resistance / load

0 (250 * ) to 800 Ohms


* These values are to be observed as minimum values during HART

TM

communication.