10 H54 Installation and operating instructions

5 Technical

Data



Accuracy class

to VDI/VDE Directive 3513, Sheet 2


1.0

Connections H 54
Flange dimensions to DIN EN 1092-1

Flange dimensions to ASME B 16.5
Pipe connection for Ermeto
Pipe connection for air cooling

DN 15 … DN 80 / PN 40
DN 80 … DN 150 / PN 16
½" … 6" class 150 lbs / RF or 300 lbs / RF
Ermeto 12
Ermeto 6, 8, 10 or 12
other on request

Overall height
With flange connection (without seals)

500 mm

Operating pressure PS
Directive 97/23/ EC of the Council of April 29, 1999 on mobile pressurized equipment (Directive for
Pressure Equipment) is applied. The maximum permissible operating pressure PS is calculated for the
maximum operating temperature TS. Both limits (PS and TS) are listed on the rating plate. As a rule PS
corresponds to the nominal pressure of the connection.
Pressure Tested PT
The pressure tested is calculated in accordance with the Directive for Pressure Equipment (97/23/EC) or AD
2000-HP30 under consideration of the maximum permissible operating pressure as well as the maximum
operating temperature.
Degree of protection
in accordance with EN 60529 / IEC 60529

IP 67, NEMA Type 4X / 6



6 Medium

Temperatures



Max. Medium Temperatures TS without electrical built-in components

-80 °C to +400 °C

Max. Medium Temperatures with ESK, K, KD
H 54 / M4 / ESK
H 54 / M4 / K ( KD )


160 °C (DN 15 : 80 °C)
180 °C (DN 15 : 100 °C)

Ambient temperature T

amb.

Ambient temperature T

amb.

with ESK, K, KD

-40°C to + 90°C
-25 °C to +60 °C

Other temperatures on request