3. Menu settings for PROFIBUS-PA

(see Section 4 in the Installation and Operating Instructions)

The following settings need to be made for operation of the IFC 090 on a PROFIBUS-PA network. Note that the

address can be set by the service ìset slave addressî as well.

Function (Fct.)

Description

3.8

TAG NO.

Text, measuring-point tag (max. 10 characters)

Characters assignable to each place:

A-Z,a-z, 0-9 or "_" (blank character)

3.9

COM

Select function for the communication port

OFF

HART

PROFI

PA

Press key

to transfer to subfunction "ADDRESS".

ADDRESS

Set address

Range:

00-15 for HART (default 00)

00-126 for PROFI PA (default 126)

Press key

to return to Fct. 3.9 COM

4. Technical data

, PROFIBUS Ident-No. F401

Hardware

Physical

to IEC 61158-2 and the FISCO model

Bus characteristics

9... 30 V; 0.3 A max.; 4.2 W max.

Base current

10 mA

FDE

yes: separate fault clearance

electronics provided

Fault current

6 mA; (fault current = max. continuous

current ñ base current)

Starting current

lower than the base current

ìExì approval

EEx ia IIC T6 or EEx ib IIC/IIB T6 in

conformity with the FISCO model

Connection

independent of polarity

Software

GSD

all KROHNE GSD files supplied on

diskette

Device profile

complete implementation of Profile B, V2.0

Functional blocks flow [m3/h], totalizer1[m3], totalizer2 [m3]

mentioned units are default units

Address range

0-126, default 126,

ìset slave addressî supported

Operator control local display and operator interface at

device

SAP`s

1; typically the number of service access

points is equal to the number of class 2

masters (operating tools)

I

I

D D

current

output

fieldbus

power

supply

U min

= 8V

bus-

connection

U max = 30V

4-20mA

B

1

D D

switching

output

fieldbus

power

supply

bus-

connection

B

1

switching

output

fieldbus

power-
supply

B

1

B

1

bus-

connection

D

D

FE

FE

current

output

fieldbus

power-

supply

D

D

I

I

U min

= 8V

U max = 30V

4-20mA

FE

FE

bus-

connection