Supplementary Documentation IFC 090, IFC 090 i with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG ∑ Ludwig-Krohne-Str. 5 R D-47058 Duisburg

4/7

Tel.: 0203-301 309 R Fax: 0203-301389 ∑ e-mail: [email protected]

1.1 GSD

All available GSD files of KROHNE devices ñ including those of the IFC 090, of course - are supplied together with

each device. The GSD contains information that is needed for project planning of the PROFIBUS-DP/PA

communication network. The relevant data files must be loaded into the project planning system/master system

before start-up of the bus system.

For example, the following applies to

COMET 200

or

COM PROFIBUS

from Siemens:

all GSD files (*.GSD) into the directory of the GSD files, e.g. *\GSD

all BMP files (*.BMP) into the directory of the bit maps, e.g. *\BITMAPS

In

STEP7,

the GSD file is automatically copied into the respective directory with ìinstall new GSDî (in the HW-Config

Menu: EXTRAS). After that, the bit map must be copied into the directory *\SIEMENS\STEP7\S7data\Nsbmp.

Following ìcatalog updatingî the device can be placed in the project. This will then enable the cyclic communication

(measured values and status).

1.2 PROFIBUS-PA profile

The IFC 090 supports the PROFIBUS-PA Profile Version 2.0. Additionally, all relevant parameters in the device are

offered via the PROFIBUS-PA interface. The IFC 090 defines the following blocks:

Three Function Blocks (FB): One Analog Input-FB for flow and two Totalizer-FBs for totalizers.

During configuration of the network you can distinguish between two different kind of totalizers. First the

temporary Profibus totalizers (PA-Tot.1/2) which will be resetted after power on. These totalizers are according

Profil 2.0. You also can choose the permanently stored device totalizers (Device-Tot.1/2). These device totalizers

will be mapped to the totalizer function blocks whereas limits and the unit of this block can be used together with

the device totalizers. Reset function is possible as well.

One transducer block for electromagnetic flow measurement.

This block provides the parameters defined in Profile 2.0.

One physical block.

This block contains the parameters defined in Profile 2.0, and also all device-specific parameters in the form of

an appendix.

1.3 Meaning of measurement and status information

During integration of the KROHNE device into the PROFIBUS master you can choose which values should be

transfered via PROFIBUS. This can be done by using the GSD file. Each value which is a 4 Byte Float Format

according IEEE Standard 754 Short Real Number a status byte follows. That means each measurement value

consists of 4 byte value plus 1 byte status. Other measurement values will directly follow as 5 Byte pakage if

configured during integration. Below the meaning of the status byte is described:

Float Format

Byte n

Byte n+1

Byte n+2

Byte n+3

Bit7

Bit6

Bit7

Bit6

Bit7

Bit7

VZ 2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

2

-16

2

-17

2

-18

2

-19

2

-20

2

-21

2

-22

2

-23

Exponent

Mantissa

Mantissa

Mantissa

Example:

40 F0 00 00 (hex) = 0100 0000 1111 0000 0000 0000 0000 0000 (binary)

Calculation:

Value = (-1)

VZ

* 2

(Exponent - 127)

* (1 + Mantissa)

Value = (-1)

0

* 2

(129 - 127)

* (1 + 2

-1

+ 2

-2

+ 2

-3

)

Value = 1 * 4 * (1 + 0,5 + 0,25 + 0,125) =

7,5