Supplementary Documentation IFC 090, IFC 090 i with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG ∑ Ludwig-Krohne-Str. 5 R D-47058 Duisburg

6/7

Tel.: 0203-301 309 R Fax: 0203-301389 ∑ e-mail: [email protected]

2. Electrical connection

(see Section 2 in the Installation and Operating Instructions)

2.1 Interconnection of devices in the hazardous location

We recommend that a PROFIBUS-PA network in the hazardous location be projected in accordance with PTBís

FISCO model (see KROHNE brochure îPROFIBUS-PA networksî). The FISCO-Model may be used, if:

all electrical components which should be connected to the bus must be approved according the FISCO model (even

the termination),

the maximum cable length does not exceed 1000 m,
the values of the cable are within the following ranges R¥=15...150

/km; L¥=0,4...1mH/km; C¥=80...200nF/km,

the approved input values of the field devices (Uo, Io, Po) are matchable with the output values of the power supply
(e.g. segmment coupler) which menas U

I

Uo,

I

I

I

o und P

I

Po.

2.2 Bus cable

Further limitations to the cable than the FISCO limitations are not existent. Nevertheless a twisted pair and shielded
cable is strongly recommended. The good quality cable could have the following data: 44

/km, <90nF/km, <3dB

attenuation at 39kHz and 100 Ohm impedance at 31,25kHz.

2.3 Shielding and grounding

For optimum electromagnetic compatibility of systems it is extremely important that the system components, and

particularly the bus cables connecting the components, be shielded and that such shields - if possible - form an

unbroken cover, electrically speaking.

Hence it follows that, for use in non-hazardous duty systems , the cable shield should be grounded as often as

possible.

In ìExì systems an adequate equipotential bonding in the hazardous and non-hazardous location along the entire

fieldbus installation is strongly recommended. Multiple grounding of the shield is also of advantage.

Note: The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of the IFC 090

cannot be assured.

2.4 PROFIBUS-PA connection

Connect the bus cable as shown in the figure.

Connect the cable cores to terminals D and D

.

Polarity reversal will not have any effect.

The cable shield should be connected with

minimum length to the FE functional ground.

The equipotential bonding conductor must be connected

to the device by connecting it to FE functional ground.