3.3.3 Set

Output2

See “Set Output1”

3.4 Calibration

The Calibration can be done for the output1 and output2. Here the following sections will describe
the detailed about the calibration screen options for the output1 lower and upper.

3.4.1 Output1

Lower

In Output1 Lower, it allows user to trim current output1.
The user starts to fix the current to 4mA, after entering the current value he reads on a voltmeter,
this value is sent to the device. This method allows adjusting to have exactly the good current
value of output1 loop.