Modbus protocol, 2 process input parameters – KROHNE GFC 300 Modbus User Manual
Page 16
6
MODBUS PROTOCOL
16
GFC 300
www.krohne.com
03/2012 - 7312402100 - AD Modbus GFC 300 R01 en
6.8.2 Process input parameters
Modbus protocol
address
Description and settings
Converter Fct.
No.
Type
Number of
registers
1st
2nd
42000
2000
Meter size
C1.1
float
2
42002
2002
GK
C1.2.2
float
2
42004
2004
Limitation min
C1.3.1
float
2
42006
2006
Limitation max
C1.3.1
float
2
42008
2008
Flow direction
C1.3.2
byte
1
42009
2009
Time constant
C1.3.3
float
2
42011
2011
Low flow cutoff threshold
C1.3.4
float
2
42013
2013
Low flow cutoff hysterese
C1.3.4
float
2
42015
2015
Plausibility error limit
C1.4.1
float
2
42017
2017
Plausibility counter decrease
C1.4.2
integer
1
42018
2018
Plausibility counter limit
C1.4.3
integer
1
42019
2019
VoS monitor function (steam only)
C1.7
byte
1
42020
2020
Matching factor (steam only)
C1.8.1
float
2
42022
2022
VoS tolerance (steam only)
C1.8.4
float
2
42024
2024
VoS time constant (steam only)
C1.8.5
float
2
42026
2026
Linearization
C1.9.1
byte
1
42027
2027
Dynamic viscosity (gas only)
C1.9.2
float
2
42029
2029
Adiabatic index (gas only)
C1.10
float
2
42031
2031
P&T correction
P&T correction
P&T correction
P&T correction (gas only)
0 = off
1 = normal
C1.11
byte
1
42032
2032
P&T inputs (gas only)
C1.12
byte
1
42033
2033
Pipe temperature (gas only)
C1.13
float
2
42035
2035
Pipe pressure (gas only)
C1.14
float
2
42037
2037
Density (gas only)
C1.15
float
2
42039
2039
Option diagnosis 1:
Option diagnosis 1:
Option diagnosis 1:
Option diagnosis 1:
1 = none
2 = velocity of sound 1
3 = gain 1
4 = SNR 1
C1.16.1
byte
1
42040
2040
Option diagnosis 2:
Option diagnosis 2:
Option diagnosis 2:
Option diagnosis 2:
1 = none
2 = velocity of sound 2
3 = gain 2
4 = SNR 2
C1.16.2
byte
1
42041
2041
Option diagnosis 3:
Option diagnosis 3:
Option diagnosis 3:
Option diagnosis 3:
1 = none
2 = velocity of sound 3
3 = gain 3
4 = SNR 3
6 = SNR
C1.16.3
byte
1