beautypg.com

Modbus protocol, 7 input registers – KROHNE GFC 300 Modbus User Manual

Page 12

background image

6

MODBUS PROTOCOL

12

GFC 300

www.krohne.com

03/2012 - 7312402100 - AD Modbus GFC 300 R01 en

6.6.2 Counter controls

6.6.3 Start calibration functions

No calibration functions have been foreseen in the Modbus Interface.

6.7 Input registers

Measurement and status values are read only and can be accessed as Modbus "Input Registers".

Function code is 04 (0x04).

Input register (3)0018 is not used for the gas option. This address has been included to have the
same layout of the higher addresses of cyclic values.

Modbus protocol
address

Description

Settings

Converter Fct. No.

3000

Start / Stop

Counter 1

Write

1

start counter

C3.1.8 / C3.1.9

Write

0

stop counter

Read

1

counter is running

Read

0

counter is stopped

3001

Start / Stop

Counter 2

Write

1

start counter

C3.2.8 / C3.2.9

Write

0

stop counter

Read

1

counter is running

Read

0

counter is stopped

3002

Start / Stop

Counter 3

1

Write

1

start counter

C3.3.8 / C3.3.9

Write

0

stop counter

Read

1

counter is running

Read

0

counter is stopped

3003

Reset Counter 1

Write

1

reset counter

C3.1.6

Write

0

-

Read

0

-

3004

Reset Counter 2

Write

1

reset counter

C3.2.6

Write

0

-

Read

0

-

3005

Reset Counter 3

1

Write

1

reset counter

C3.3.6

Write

0

-

Read

0

-

1 Only available in converters with IO2. A write attempt to a non-existing counter will cause an error response.