MODBUS PROTOCOL

6

11

GFC 300

www.krohne.com

03/2012 - 7312402100 - AD Modbus GFC 300 R01 en

6.5 Device identification on the Modbus interface

The device identification is according to the category "Regular" according to the Modbus
Application Protocol Specification V1.1a. Function code 43 / 14 (0x2B / 0x0E).

6.6 Coil registers

These function codes are used for access:

• 0x01 = read input coil
• 0x05 = write single coil

6.6.1 Converter controls

Modbus
object Id

Object name / Description

Type

GDC Object
Number

Content

0x00

VendorName

16 Byte ASCII

ASCII String

24730.32

KROHNE

0x01

ProductCode

10 Byte ASCII String

32519.32

(24731.32)

CG number (order code for the

converter assembly)

0x02

MajorMinorRevision

7 Byte ASCII String

24732.32

V1.1.xx

0x03

Vendor URL

32 Byte ASCII String

24733.32

www.krohne.com

0x04

ProductName

16 Byte ASCII String

24734.32

GFC 300

0x05

ModelName

16 Byte ASCII String

24735.32

Modbus

0x06

UserApplicationName

16 Byte ASCII String

24736.32

User tag, displayed on the header

of the local screen

Coil address

Function

1000

Write 1 generates a cold start, write 0 is ignored

1001

Write 1 generates a warm start, write 0 is ignored

1002

Write 1 generates an error reset, write 0 is ignored