MODBUS PROTOCOL
6
11
GFC 300
www.krohne.com
03/2012 - 7312402100 - AD Modbus GFC 300 R01 en
6.5 Device identification on the Modbus interface
The device identification is according to the category "Regular" according to the Modbus
Application Protocol Specification V1.1a. Function code 43 / 14 (0x2B / 0x0E).
6.6 Coil registers
These function codes are used for access:
• 0x01 = read input coil
• 0x05 = write single coil
6.6.1 Converter controls
Modbus
object Id
Object name / Description
Type
GDC Object
Number
Content
0x00
VendorName
16 Byte ASCII
ASCII String
24730.32
KROHNE
0x01
ProductCode
10 Byte ASCII String
32519.32
(24731.32)
CG number (order code for the
converter assembly)
0x02
MajorMinorRevision
7 Byte ASCII String
24732.32
V1.1.xx
0x03
Vendor URL
32 Byte ASCII String
24733.32
www.krohne.com
0x04
ProductName
16 Byte ASCII String
24734.32
GFC 300
0x05
ModelName
16 Byte ASCII String
24735.32
Modbus
0x06
UserApplicationName
16 Byte ASCII String
24736.32
User tag, displayed on the header
of the local screen
Coil address
Function
1000
Write 1 generates a cold start, write 0 is ignored
1001
Write 1 generates a warm start, write 0 is ignored
1002
Write 1 generates an error reset, write 0 is ignored