ELECTRICAL CONNECTIONS
4
9
DK32 DK34
www.krohne.com
03/2013 - 4002598201 AD DK32/34 NEPSI Ex i R01 en
Electrical connections
4.1 General notes
For version DK3./../../S/../A-Ex (plug), the separate intrinsically safe signal circuits with level of
protection "ia" or "ib" are electrically connected in the terminal compartment of the plug
housing and for version DK3./../../L/../A-Ex (connecting cable) it is the connecting cable as
illustrated in the connection diagram. Permissible maximum values (electrical data) must be
observed.
Connecting cable
The connecting cables must be selected according to prevailing installation standards. The outer
diameter of the connecting cable must be within the sealing range of the cable entry. The
connecting cables must be fixed and laid in such a way as to be sufficiently protected against
damage.
All cores that are not used must be securely connected to the earth potential of the hazardous
area or carefully insulated against each other and against earth (test voltage ≥ 500 V
eff
).
Cable entries / Blanking plugs
The DK3./../../S/../A-Ex variable area flowmeter is equipped with a connector. The connector
guarantees protection from foreign bodies and water (protection category) IP65. The cable entry
is closed with a plug. The plug is to be replaced with a suitable connecting cable (nominal
diameter range 6...9mm).
Connection diagrams
Contact connection
Cable colors of assembled cable
1
Min minus
white
2
Min plus
yellow
3
Max minusMax minus
green
4
Max plus
brown
5
Lift slot
6
Fastening screw of connection box