KROHNE ALTOFLUX IFM 4080 K EEx EN User Manual
Page 10
9
MODIS modul
Nominal values for voltage and current
P-SA
(passive current output )
Current:
4 .. 20 mA
Working voltage:
8 .. 30V
Voltage drop :
8V at 4mA
FA-ST
(frequency/pulse/status output
or control input)
Working voltage:
6 .. 30V
Working current:
< 110 mA
Voltage drop: in ON-state:
< 2V at 110 mA
Leakage current in OFF-state:
< 900
µ
A at 30V
Control input:
Input voltage LOW level:
< 3V
Input voltage HIGH level:
> 7V
Frequency range :
0 .. 12 KHz
DC-I
(active voltage source)
Voltage:
20V
Current
30 mA
Internal resistance:
260
Table 8: Nominal voltage and current values for the MODIS modules
IFC 090i-EEx version
Part No.
MODIS modules
Terminal designation
Ex-i1
2.11582.01.00
P-SA
FA-ST
I
⊥
I
B1
B1
⊥
Ex-i2
2.11582.03.00
P-SA
F-PA
I
⊥
I
D
D
⊥
Ex-i3
2.11582.02.00
P-SA
DC-I
I+
I
Ex-i4
2.11582.05.00
FA-ST
F-PA
B1
B1
⊥
D
D
⊥
Ex-i5
2.11582.06.00
FA-ST
DC-I
B1+
B1
Ex-i6
2.11582.07.00
FA-ST
FA-ST
B2
B2
⊥
B1
B1
⊥
Ex-i7
2.11582.08.00
P-SA
F-FF
I
⊥
I
D
D
⊥
Ex-i8
2.11582.09.00
FA-ST
F-FF
B1
B1
⊥
D
D
⊥
Table 9 : IFC 090i-EEx 24 Vac/dc versions.
IFC 090i-EEx version
Part No.
MODIS modules
Terminal designation
Ex-i1
2.12253.01.00
P-SA
FA-ST
I
⊥
I
B1
B1
⊥
Ex-i2
2.12253.02.00
P-SA
F-PA
I
⊥
I
D
D
⊥
Ex-i4
2.12253.03.00
FA-ST
F-PA
B1
B1
⊥
D
D
⊥
Ex-i6
2.12253.04.00
FA-ST
FA-ST
B2
B2
⊥
B1
B1
⊥
Ex-i7
2.12253.05.00
P-SA
F-FF
I
⊥
I
D
D
⊥
Ex-i8
2.12253.06.00
FA-ST
F-FF
B1
B1
⊥
D
D
⊥
Table 10: IFC 090i-EEx 100-230 Vac versions.
Due to mechanical and electrical limitations, only the in table 9 and 10 listed pairs of MODIS
modules are possible. The two modules each use two terminals of the bottom four terminals
of the flameproof terminal feed-through in the dividing wall between the electronics and
terminal compartment of the signal converter housing, except for the combination with
module DC-I (only applicable for 24 Vac/dc versions), where only two of the four terminals
are used. Interconnection of the two modules, P-SA and DC-I resp. FA-ST and DC-I is made
internally.