KROHNE VARIFLUX IFM 6080 K-EEx-i-EEx EN User Manual
Page 19

ALTOFLUX IFM x080 K-EEx and ALTOFLUX IFM x080 K / i-EEx
19
Connection diagrams 1 to 4 of the intrinsically safe signal in-/outputs
1
Current output I
active
2
Current output I
passive
Version: Ex-i3
Versions:
Ex-i1, Ex-i2, Ex-i7
I = 4 - 20 mA
U
ext
= 8.1 - 30 V
R
i
= 350
Ω
I = 4 - 20 mA
R
i
≤ (U
ext
- 8) / 0.022
IFC 090 i-EEx
IFC 090 i-EEx
hazardous area
hazardous area
safe area or
safe area or
hazardous area (
*
)
hazardous area (
*
)
3
Pulse output P
active
4
Pulse output P
passive
Version: Ex-i5
Versions:
Ex-i1, Ex-i4, Ex-i6, Ex-i8
U
int
= 20 V DC
U
ext
= 6 - 30 V DC
R
int
= 260
Ω
I
max
≤ 110 mA
U
L
= 20×R
L
/ (260+R
L
)
IFC 090 i-EEx
IFC 090 i-EEx
hazardous area
hazardous area
safe area or
safe area or
hazardous area (
*
)
hazardous area (
*
)
passive
counter
with
external supply
(
*
) Important note:
Only if the measuring devices are also explosion protected !