beautypg.com

Technical data, 8 sensor response times – KROHNE OPTITEMP TRA-TCA EN User Manual

Page 57

background image

TECHNICAL DATA

7

57

OPTITEMP TRA/TCA

www.krohne.com

08/2010 - 4000630501 - MA OPTITEMP TRA/TCA R01 en

7.8 Sensor response times

Thermometer response times are generally indicated as "50% time" (t

05

) and "90% time" (t

09

).

"50% time" refers to the time needed for a thermometer signal to achieve 50% of its end value in
the face of erratic temperature changes (this applies analogously to "90% time")

Pt100-RTD, water with 0.4 m/s (1.31 ft/s)

Thermocouple, water with 0.4 m/s (1.31 ft/s)

The following table contains information regarding the response times of the thermometer
without thermowell (TRA/TCA-P14):

Without thermowell (TRA/TCA-P14 with Ø 6 mm / 0.24")

INFORMATION!
You can find more information about response times in VDI 3522.

Ø of thermowell

Straight thermowell

Reduced tip

Tapered tip

[mm]

["]

t

05

(s)

t

09

(s)

t

05

(s)

t

09

(s)

t

05

(s)

t

09

(s)

9

0.35

17

52

Not available

Not available

11

0.43

21

58

8

22

Not available

12

0.47

22

66

10

26

12

30

Ø of thermowell

Straight thermowell

Reduced tip

Tapered tip

[mm]

["]

t

05

(s)

t

09

(s)

t

05

(s)

t

09

(s)

t

05

(s)

t

09

(s)

9

0.35

14

42

Not available

Not available

11

0.43

17

46

7

18

Not available

12

0.47

18

54

8

21

10

24

sensor

Water with 0.4 m/s (1.31 ft/s)

Air with 1 m/s (3.28 ft/s)

t

05

(s)

t

09

(s)

t

05

(s)

t

09

(s)

Pt100 RTD

3.5

8

24

54

Thermocouple

2.5

7

21

50

.book Page 57 Tuesday, August 17, 2010 12:18 PM