The chronological sequence of pfd – KROHNE OPTISWITCH 3x00C 2wire SIL EN User Manual

Page 23

background image

Overflow protection

(max. operation)

Dry run protection

(min. operation)

PFD

avg

T

Proof

=

1 year

T

Proof

=

5 years

T

Proof

=

10 years

<

0.016 x 10

-2

<

0.078 x 10

-2

<

0.156 x 10

-2

<

0.016 x 10

-2

<

0.081 x 10

-2

<

0.162 x 10

-2

PFH

<

0.036 x 10

-6

/h

<

0.037 x 10

-6

/h

The chronological sequence of PFD

avg

is nearly linear to the

operating time over a period up to 10 years. The above values
apply only to the T

Proof

interval after which a recurring function

test must be carried out.

1

5

10

T

Proof

PFD

avg

1

2

3

4

Fig. 1: Chronological sequence of PFD

avg

(figures see above charts)

1

PFD

avg

= 0

2

PFD

avg

after 1 year

3

PFD

avg

after 5 years

4

PFD

avg

after 10 years

Multiple channel architecture

If the measuring system is used in a multiple channel
architecture, the safety-relevant characteristics of the selected
structure of the meas. chain must be calculated specifically for
the selected application according to the above failure rates.

A suitable Common Cause Factor must be taken into account.

Time-dependent proc-
ess of PFD

avg

Specific characteristics

OPTISWITCH series 3000 • - two-wire

23

Functional safety

32745

-

EN

-

080414