Mode switch on the sensor to " min, Mode switch on the sensor to " max, Single channel architecture (1oo1d) – KROHNE OPTISWITCH 3x00C 2wire SIL EN User Manual

Page 22: Fault reaction time specific characteristics

background image

Overflow protection

(max. operation)

Dry run protection

(min. operation)

Mode switch on the
sensor to "min."

Overflow protection

(max. operation)

Dry run protection

(min. operation)

λ

sd

39 FIT

45 FIT

λ

su

373 FIT

361 FIT

λ

dd

168 FIT

173 FIT

λ

du

36 FIT

37 FIT

DC

S

9 %

11 %

DC

D

82 %

82 %

MTBF = MTTF + MTTR

1.59 x 10

6

h

1.59 x 10

6

h

Diagnosis test period

<

100 sek.

Single channel architecture (1oo1D)

SIL

SIL

2

HFT

0

Sensor type

Type B

Mode switch on the sensor to "max."

Overflow protection

(max. operation)

Dry run protection

(min. operation)

SFF

97 %

93 %

PFD

avg

T

Proof

=

1 year

T

Proof

=

5 years

T

Proof

=

10 years

<

0.008 x 10

-2

<

0.039 x 10

-2

<

0.077 x 10

-2

<

0.019 x 10

-2

<

0.093 x 10

-2

<

0.186 x 10

-2

PFH

<

0.018 x 10

-6

/h

<

0.043 x 10

-6

/h

Mode switch on the sensor to "min."

Overflow protection

(max. operation)

Dry run protection

(min. operation)

SFF

94 %

94 %

Fault reaction time

Specific characteristics

22

OPTISWITCH series 3000 • - two-wire

Functional safety

32745

-EN