KROHNE OPTISWITCH 5200C Contactless EN User Manual
Page 18
SW E60C
2 0 - 2 5 3 V A C / D C
m a x 4 0 0 m A
A
B
L
N
L
N
1 2
0,5 g / cm3
0,7 g / cm3
+
+
1 2
1 2
3
5
1
2
4
Fig. 11: Electronics and connection compartment, single chamber housing
1
Control lamp
2
DIL switch for mode adjustment
3
DIL switch for switching point adaptation
4
Ground terminal
5
Screwed terminals
We recommend connecting OPTISWITCH 5200 C, 5250 C in
such a way that the switching circuit is open when there is a
level signal, line break or failure (safe condition).
The contactless electronic switch is always shown in non-
operative condition.
The instrument is used for direct control of relays, contactors,
magnet valves, warning lights, horns etc. It must not be
operated without an intermediately connected load, because
the electronics would be destroyed if connected directly to the
mains. It is not suitable for connection to low voltage PLC
inputs.
Domestic current is temporarily lowered below 1 mA after
switching off the load so that contactors, whose holding current
is lower than the constant domestic current of the electronics,
are reliably switched off.
When OPTISWITCH 5200 C, 5250 C is used as part of an
overfill protection system acc. to WHG, also note the
regulations of the general type approval.
Electronics and connection
compartment
Wiring plan
18
OPTISWITCH 5200 C, 5250 C - with contactless electronic switch
Connecting to voltage supply
30433
-EN
-060831