3.1.4.

I/O functions

The following limit values need to be taken into account when connecting the I/O interfaces of the
BM 70..-Ex level gauges:

BM 70./.-Ex with non-intrinsically safe I/O functions

I/O function

(1)

Nominal values of the non-

certified receiver instrument

Additional restriction

Acc. to standard Installation &

Operating Instructions

Acc. to standard Installation &

Operating Instructions

Power for receiver instruments,

max. 250 V

(1)

Only for connection to circuits with “functional extra-low voltage with safety separation (PELV)“

BM 70A/.i-Ex and BM 70Pi/.-Ex with intrinsically safe I/O functions

I/O function

Identifying marking

Maximum safety values

Passive current output

Ex ia IIC or
Ex ib IIC

Ui = 30V

Ii = 250mA

Pi = 1,0W

Ci = 5nF

Li = negligible

Passive switching output

Ex ia IIC or
Ex ib IIC

Ui = 30V

Ii = 250mA

Pi = 1,0W

Ci = 5nF

Li = negligible

Interface
PROFIBUS-PA

(1)

Ex ia IIC or
Ex ib IIC/IIB

Ui = 30V

Ii = 380mA

Pi = 5,32W

Ci = 5nF

Li = negligible

Interface
Fieldbus FF

Ex ia IIC or
Ex ib IIC/IIB

Ui = 30V

Ii = 380mA

Pi = 5,32W

Ci = 5nF

Li = negligible

(1)

Suitable for connection to intrinsically safe fieldbus systems based on the FISCO Model



The intrinsically safe circuits of the I/O functions are galvanically isolated both from ground and also
from each other (test voltage > 500 VAC).
Furthermore, all intrinsicaly safe circuits are safety-separated from the non-intrinsically safe power
circuits up to a peak voltage of 375 V.

BM 702-Ex / BM 702 A-Ex with intrinsically safe I/O functions

I/O functions

Identifying marking

Maximum safety values

Passive current output

Ex ia IIC or
Ex ib IIC

Ui = 30V

Ii = 250mA

Pi = 1,0W

Ci = 11nF

Li = negligible



The intrinsically safe circuit is galvanically isolated from ground (test voltage > 500 VAC).