Fig. 12: Agitators

Do not mount the instruments in or above the filling stream.

Make sure that you detect the product surface and not the

inflowing product.

Fig. 13: Inflowing liquid

Through the action of filling, stirring and other processes in the

vessel, dense foams which considerably damp the emitted

signals may form on the product surface.
If foams are causing measurement errors, the sensor should

be used in a standpipe or, alternatively, the more suitable

guided radar sensors (TDR) should be used.

Inflowing material

Foam

OPTISOUND 3010 C - 4 … 20 mA/HART