4.2 Mounting information

Screw OPTISOUND 3010 C into the mounting socket with an

appropriate spanner applied to the hexagon of the process

fitting. Max. torque see chapter "Technical data".

Warning:

The housing must not be used to screw the instrument in!

Applying tightening force to the housing can damage its

internal mechanical components.

When mounting OPTISOUND 3010 C, keep a distance of at

least 200 mm (7.9 in) to the vessel wall. If the sensor is

installed in the center of dished or rounded vessel tops,

multiple echoes can arise. These can, however, be faded out

by an appropriate adjustment (see chapter "Setup").
If this distance cannot be maintained, a false echo storage

should be carried out during setup. This applies particularly if

buildup on the vessel wall is expected. In this case, we

recommend repeating the false echo storage later on with

existing buildup.

1

2

> 200 mm

Fig. 5: Mounting on dished vessel tops

1

Reference plane

2

Vessel center or symmetry axis

In vessels with conical bottom it can be advantageous to

mount the sensor in the center of the vessel, as measurement

is then possible down to the lowest point of the vessel bottom.

Screwing in

Installation position

OPTISOUND 3010 C - 4 … 20 mA/HART

11

Mounting

30503

-EN