3.3.3 Frequency (pulse) output F

The frequency output is galvanically isolated from all input and output circuits but not from current output I.

Therefore only one grounded receiver instrument may be connected to either frequency output F or current output
I.

·

·

·

·

·

·

All functions and operating data are programmable, see Section 5, 6.1 & 6.2.9.
Factory - set data and functions are listed in the enclosed report on settings. This can also be used to record any

changes made to the operating parameters.

Active frequency output for electromechanical totalizers EMC (terminals 4.1/4.2) or for electronic totalizers EC

(terminals 4.1/4.2 or 4/4.1/4.2), 10 to 36000000 pulses/hr (0.0028 to 10000 Hz), amplitude max. 30 V, selectable
pulse widths and load rating see below.

Passive frequency output, open collector for connection of active electronic counters EC or switchgear, input

voltage 5 to 30V, load current max. 100 mA, R

i

= 100 ohms, selectable pulse widths see below.

Pulse width (Fct. 1.4.3) as a factor of frequency f (pulse rate) and maximum permissible load for active output

(term. 4.1/4.2 or 4/4.1/4.2), see also Sect. 6.2.9.

Pulse width

Frequency f = F

100%

Load rating of active output

Load current

Load

500 ms

0.0028 Hz

< f

£

1 Hz

< 150 mA

³160 Ohm

200 ms

0.0028 Hz

< f

£

2 Hz

< 150 mA

³160 Ohm

100 ms

0.0028 Hz

< f

£

3 Hz

< 150 mA

³160 Ohm

100 ms

3 Hz

< f

£

5 Hz

< 60 mA

³400 Ohm

50 ms

0.0028 Hz

< f

£

5 Hz

< 150 mA

³160 Ohm

50 ms

5 Hz

< f

£

10 Hz

< 60 mA

³400 Ohm

30 ms

0.0028 Hz

< f

£

6 Hz

< 150 mA

³160 Ohm

30 ms

6 Hz

< f

£

10 Hz

< 80 mA

³300 Ohm

Pulse duty cycle 1:1*

10 Hz

< f

£

1000 Hz

< 25 mA

³1000 Ohm

160 µs*

1000 Hz

< f

£

2547 Hz

< 25 mA

³1000 Ohm

50 µs*

2547 Hz

< f

£

10000 Hz

< 25 mA

³1000 Ohm

* fixed pulse width, independent of programming in Fct. 1.4.3

Refer connection diagrams

k, l and m. Refer to Section 3.3.4

·
·

Output characteristics

3.3.4 Connection diagram for outputs

j to m

Current output I: Diagrams I1 in Section 6.2.8

7