beautypg.com

Electrical connections – KROHNE OPTISONIC 6300 EEx EN User Manual

Page 17

background image

ELECTRICAL CONNECTIONS

4

17

OPTISONIC 6300

www.krohne.com

03/2010 - 7309972300 - EX OPTISONIC 6300 R03 en

The exact I/O-configuration for circuits A, B, C and D is order-specific and can be determined by
the CG34 number shown on the I/O sticker inside the terminal compartment. Therefore check
the data on the back of the UFC 300 electronics unit. The CG34 number contains 10 characters of
which the last three characters (XYZ) determine the configuration of the I/O circuits:

For schematic overviews of the CG34 numbers, refer to

"Ex i" I/O connections

on page 19 and

refer to

Non-"Ex i" I/O connections

on page 18. These overviews do not show all details. The

exact connection diagram of a specific UFC 300 signal converter can be found on the sticker
inside the terminal compartment.

For use in gaseous hazardous areas:

For use in gaseous hazardous areas:

For use in gaseous hazardous areas:

For use in gaseous hazardous areas: The chosen cable glands must have the appropriate type of
protection for the terminal compartment that is increased safety (Ex e) or flameproof enclosure
(Ex d). They MUST be suitable for the conditions of use and correctly installed.

The flowmeter with the terminal compartment in type of protection increased safety “Ex e” is
factory supplied with two “Ex e” approved cable glands and one “Ex e” approved blanking element
(i.e. stopping plug).

The wiring of instruments has to be in accordance with the requirements as specified in the
relevant national or international standard for electrical installations in hazardous areas, e.g.
EN 60079-14. Section 9 (wiring systems) of this standard applies to all types of protection.
Section 10 (additional requirements for type of protection “d” - flameproof enclosures), section
11 (additional requirements for type of protection “e” - increased safety) and section 12
(additional requirements for type of protection “i” - intrinsic safety) apply to respectively “Ex d”,

Ex e” and “Ex i” performed connection (terminal) compartments.

CG34

CG34

CG34

CG34

****

****

****

X

XX

X

YYYY

Z

ZZ

Z

Pos 1...4

5

6

7

8

9

10

determine I/O circuits

WARNING!
The flowmeter with the terminal compartment performed as flameproof enclosure

Ex d

is

supplied with one

Ex d

approved stopping plug and two temporary plugs. The temporary plugs

are only intended for sealing the housing against entry of dust, moisture or else during
transport, handling and storage. These temporary plugs must be replaced by suitable

Ex d

approved cable glands, stopping plugs or conduit adapters with sealing devices before the
flowmeter is put into operation. Unused openings must be sealed by suitable certified plugs.